(Major) Fixed an issue that could trigger a watchdog reset when entering low power mode. This issue was observed on the CR350 when a user-defined program was running and the datalogger entered low power (sleep) mode. If the logger was later awakened via USB activity, a watchdog reset could occur during the power state transition.
(Major) Improved reliability of large file transfers using Microhard modem.
(Major) Updated IP stack sleep configuration to fix a Hard Fault watchdog.
(Major) Fixed a memory issue that could cause a Hard Fault watchdog when running FTPClient().
(Major) Resolved a DNP3 issue that could result in the logger returning incorrect values.
(Minor) Enabled UID retrieval/assignment over remote encrypted PakBus connections using DevConfig.
(Minor) Increased cellular modem boot wait time to address SIM registration issues with certain cards.